RSDB(450/550/650/750)G

RSDB450G, RSDB550G,RSDB650G, and RSDB750G Power Supplies


RSDB750G -1 RSDB750G -2 RSDB750G -3

The RSDB450G, RSDB550G,RSDB650G, and RSDB750G power supplies are capable of “HOT SWAP” exchanging with active current sharing and OR-ing isolation MOSFETs built in for +12V output, and droop current sharing and OR-ing isolation diode built in for +5Vsb output. The DC -48V input is rated -36VDC to -60VDC/-72VDC. A 38mm high reliable Sanyo Denki fan is installed to the power supply module for cooling the power supply module.

Input and Output Characteristics

Input
Parameter Min Nominal Input Max
Vin Voltage RSDB450G
Vin Voltage RSDB550G
Vin Voltage RSDB650G
Vin Voltage RSDB750G
-36 VDC
-36 VDC
-42 VDC
-45 VDC
-48 VDC
-48 VDC
-48 VDC
-48 VDC
-60/-72 VDC
-60/-72 VDC
-60/-72 VDC
-60/-72 VDC
Vin Current RSDB450G
Vin Current RSDB550G
Vin Current RSDB650G
Vin Current RSDB750G
20.0A
Output
Parameter +12V +5VSB
Min. Current 2.0A 0.0A
RSDB450G O/P Max. Current
RSDB550G O/P Max. Current
RSDB650G O/P Max. Current
RSDB750G O/P Max. Current
37.0A
45.0A
54.0A
62.5A
3.0A
3.0A
3.0A
3.0A

Environmental Reqirements

Operating Temperature -10-50°C
Operating Humidity 10-90%
Altitude (Operating) 3000m (10000ft)

EMC and Safety Regulations

EMC FCC Part 15 and EN55022:2006 meeting Class A
EN 55024: 1998+A1: 2001+A2: 2003
EN 55022:2006+A1:2007 Class A
EN 55024:1998+A1:2001+A2:2003, including
IEC 61000-4-2:2009 ESD Level 3: Air ±8KV; Level 2: Contact ±4KV Criterion B
IEC 61000-4-3:2006+A1:2008+A2:2010 RF field susceptibility, Level 2 3V/m Criterion A
IEC 61000-4-4:2004+A1:2010 EFT bursts, Level 2: DC Line, 0.5KV Criterion B
IEC 61000-4-5:2006 Surge susceptibility, Level 1, DC Line to Line, 0.5KV Criterion B
IEC 61000-4-6:2009 Conducted susceptibility, EN61000-4-6, Level 2, DC Line, 3V Criterion A
IEC 61000-4-8:2010 Magnetic field immunity, Level 1, 1A/m, 50Hz for 5 min. Criterion A
Safety cUL UL 60950-1 (substituted by cTUVus)
TUV EN 60950-1:2006+A11+A1+A12
CB IEC 60950-1:2005 (2nd Edition)+Am1:2009
CCC

Function and Reliability

Protection Over Voltage Protection
Over Current Protection
Short-circuit Protection
No-Load Protection
MTBF 100K hours minimum at full load 25°C per Bellcore_TR-332_ISSUE6